CSV-A8 AC Current Switch Sensor

CSV-A8

Measure runtime (time-of-use) of equipment with the CSV-A8 split-core AC current sensor along with a compatible HOBO data logger. This UL-listed sensor has built-in on/off status lights and provides an adjustable current threshold of 0.5 to 175 amps. Simply install the sensor around a current-carrying wire to the equipment to be monitored and then connect the sensor to a compatible UX90 or UX120-017 data logger.

  •     Can be used with any state channel on UX120-017, UX90-001 or UX90-004 data loggers
  •     Installs around a current-carrying wire to provide a relay signal indications equipment on/off
  •     Adjustable threshold provides maximum application flexibility
  •     UL listed

Specifications


Amperage range: .5 to 175 Amps continuous
Sensor supply voltage: Induced from monitored conductor, with no external power required
Isolation: 600 VAC rms (max voltage when monitoring an uninsulated conductor
Status ratings: N.O. 1.0A @ 30 VAC/DC max, not polarity-sensitive
Dimensions: 5.9 x 5.1 x 2.3 cm
Window opening: 1.27 cm x 1.52 cm