EG4100 Series Current Transformer Sensor

T-EG-0390-0050 50

Split-core CTs from J&D Sensing offer a well constructed hinged body and are accurate to +/-1% from 1%-100% of their stated current rating. The small interval for physical size options (10mm/0.39", 24mm/0.94", and 36mm/1.42") allow for a flexible installation. Each CT size has a hinge and clipping mechanism, making it easy to close the CT in tight situations.

Choose

Highlighted Features


    Multiple current ratings
    Small size, light weight
    Simple installation
    Overvoltage protection circuit
    Pin-hinged at pivot point


The T-EG-xxxx-xxxx sensor supports the following measurements: AC Current and Amps (A)

Technical Specifications

  • 333 mVrms at rated output
  • Accurate within 1% from 1% to 100% of rated amperage
  • Operates 50Hz/60Hz
  • Maximum primary insulation up to 600 Vrms
  • 8' twisted pair lead with CT connector

Model Description
T-EG-0390-0050 50 Amp Split-core CT (0.39" opening)
T-EG-0390-0075 75 Amp Split-core CT (0.39" opening)
T-EG-0630-0050 50 Amp Split-core CT (0.63" opening)
T-EG-0630-0100 100 Amp Split-core CT (0.63" opening)
T-EG-0940-0100 100 Amp Split-core CT (0.94" opening)
T-EG-0940-0200 200 Amp Split-core CT (0.94" opening)
T-EG-1420-0400 400 Amp Split-core CT (1.42" opening)
T-EG-1420-0600 600 Amp Split-core CT (1.42" opening)

 

Model A B C D E Opening
T-EG-0390-XXXX 1.59” 0.91” 0.93” 1.05” 0.57” 0.39”
T-EG-0630-XXXX 1.77” 1.02” 1.18” 1.24” 0.74” 0.63”
T-EG-0940-XXXX 2.56” 1.48” 1.77” 1.33” 0.83” 0.94”
T-EG-1420-XXXX 3.24” 1.89” 2.25” 1.58” 0.83” 1.42”